1. Home
  2. Docs
  3. View User Manual
  4. BASIS OF DESIGN > ELEC...
  5. TRANSFORMER PROPERTIES DATABASE

The following transformer properties are used by the HST Software when sizing transformers and calculated losses. Where an exact Power and Voltage Rating match is not available, the HST Software selects the closest matching Power and Voltage rating:

 

HV Rating (kV)Base S (MVA)Top S (MVA)Z% (%)X/RLC,% (%)
34.544680.13
69610815.50.1
691220818.60.8
691830823.70.8
692440827.30.6
693050829.50.6
693660834.10.5
694270834.10.5
694880834.10.5
695490834.10.5
6960100834.10.5
69901508420.4
691202008420.4
691502508500.4
691803008500.4
1156108.515.50.1
11512208.518.60.8
11518308.523.70.8
11524408.527.30.6
11530508.529.50.6
11536608.534.10.5
11542708.534.10.5
11548808.534.10.5
11554908.534.10.5
115601008.534.10.5
115901508.5420.4
1151202008.5420.4
1151502508.5500.4
1151803008.5500.4
138610915.50.1
1381220918.60.8
1381830923.70.8
1382440927.30.6
1383050929.50.6
1383660934.10.5
1384270934.10.5
1384880934.10.5
1385490934.10.5
13860100934.10.5
138901509420.4
1381202009420.4
1381502509500.4
1381803009500.4
2306101015.50.1
23012201018.60.8
23018301023.70.8
23024401027.30.6
23030501029.50.6
23036601034.10.5
23042701034.10.5
23048801034.10.5
23054901034.10.5
230601001034.10.5
2309015010420.4
23012020010420.4
23015025010500.4
23018030010500.4
34561014.515.50.1
345122014.518.60.8
345183014.523.70.8
345244014.527.30.6
345305014.529.50.6
345366014.534.10.5
345427014.534.10.5
345488014.534.10.5
345549014.534.10.5
3456010014.534.10.5
3459015014.5420.4
34512020014.5420.4
34515025014.5500.4
34518030014.5500.4
50061014.515.50.1
500122014.518.60.8
500183014.523.70.8
500244014.527.30.6
500305014.529.50.6
500366014.534.10.5
500427014.534.10.5
500488014.534.10.5
500549014.534.10.5
5006010014.534.10.5
5009015014.5420.4
50012020014.5420.4
50015025014.5500.4
50018030014.5500.4
Was this article helpful to you? No Yes