1. Home
  2. Docs
  3. View User Manual
  4. BASIS OF DESIGN > ELEC...
  5. CONDUCTOR PROPERTIES DATABASE – METRIC UNITS

The following conductor properties are used by the HST Software when sizing conductors for projects in Metric units for the following cable types:

  • String Conductors
  • DC Feeders
  • LV AC Feeders
  • MV AC Feeders
  • Bare Ground Conductors
Trade SizeArea (mm^2)Diameter (mm)No. StrandsUnit
111.297mm^2
1.51.51.567mm^2
2.52.52.017mm^2
442.557mm^2
663.127mm^2
10104.057mm^2
16165.137mm^2
25256.397mm^2
35357.567mm^2
50509.157mm^2
707010.8619mm^2
959512.619mm^2
12012014.1519mm^2
15015015.8519mm^2
18518517.6419mm^2
24024020.0937mm^2
30030022.4637mm^2
40040025.9737mm^2
50050029.0537mm^2

 

 

The following conductor properties are used by the HST Software when sizing conductors for projects in Metric units for the following cable types:

  • Overhead Conductors
Trade SizeArea (mm^2)Diameter (mm)No. StrandsUnit
2002000.74318mm^2
2402400.81418mm^2
2802800.87918mm^2
3203200.9418mm^2
4004001.0436mm^2
4804801.16545mm^2
6406401.34545mm^2
8008061.50445mm^2
9009001.60284mm^2
110011001.73584mm^2
Was this article helpful to you? No Yes

How can we help?

CONDUCTOR PROPERTIES DATABASE - METRIC UNITS